Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction
Power supply specification
Main supply voltage: 12Vdc to 28 Vdc
Nominal main supply voltage: 24 Vdc
Quiescent current (24 Vdc): 140µA without base isolator / 240µA with base isolator
Alarm current (24 Vdc): 5mA ± 1mA
Fault current (24 Vdc): 140µA
Remote alarm indicator output: Individual command: 5mA ± 1mA
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -30°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
Standard EN54-7 Ed2000
Security addressing
CE certified according to CPD
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OA05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
OA05 is dedicated to interactive fire detection panels.
The smoke detector OA05 is designed to be installed under flat ceiling with heights ranging between 2,5 m
and 12 m and this, in healthy and more or less ventilated buildings.
The maximum supervised surface is 80m² by detector; however it is preferable to refer to the local rules of
installation recommended in particular when the characteristics of the installation differ from those stated
above. Eight levels of sensitivity are available while programming the fire detection panel (from 0,1dB/m to
0,35 dB/m).
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Addressable smoke detector (SD3) OA05” Cancel reply
Related Products
-
0 out of 5
Global Fire Addressable Panel JUNO NET
- Fully expandable system from 1-96 Loops with distributed intelligence for added security
- Up to 256 devices per loop (TBA)
- Up to 96 Loop sounders with 32 individually programmable addresses per Loop
- Compatible with major analogue addressable communications protocols
- 2 Fire output changeover relays and 1 Fault output relay (NC)
- Open collector outputs for Fire, Fault and pre-alarm remote indication
- 2 fully monitored sounder outputs on main panel and each sub panel
- Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card)
- Redundant network communication via RS485, TCP/IP & Fiber Optics
- 384 programmable zones
- 512 fully programmable sounder and I/O groups
- Event Log 2000 entries FIFO
- Backlit LCD display 4 row * 40 characters
- Multiple programming options, onboard keypad, Remote IR(optional), PS2 Keyboard and GFE Connector software
- Windows™ based PC Graphics package ODYSSEY for alarm management and reporting(Optional)
- Multiple Language support (menu selectable)
- MODBUS (ASCII & RTU) and BMS support
-
0 out of 5
Conventional Sounder VALKYRIE CS
VALKYRIE CS
Conventional Wall Mount Sounder/ Beacon
The VALKYRIE CS is a wall mounted Conventional Sounder/ Beacon with low power consumption. Four different
tones are available and selected using DIL switches 1 and 2.
Both continuous and pulsing outputs are provided via separate negative supply connections allowing for the
presence of differentiated evacuation and alert sounds. -
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
-
0 out of 5
HEPHAIS 128 2 Loops Addressable Panel
Main characteristics
2 loops (128 addr./loop) or 4 open circuits (32
det./line)
99 zones, 99 groups of command
1000 memory events
Pre-alarm mode, day/night mode
Manual/automatic activation of sounders line
2 programmable inputs + 5 programmable relay
outputs
Very easy to program and install
Self-learning of detectors on the loop
Programmable by keyboard or software
downloading/uploading
4 lines, 40 characters LCD display