ALPHA 2 – 2 zones fire detection conventional panel
Main characteristics
2 monitored conventional lines
Maximum 32 detectors and/or manual call
points per line
Monitored sounders line
Auto powered sounders line
External power supply outputs
Programmable open collector output
Level 2 access code.
Easy management
Small size plastic box
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
2 monitored conventional lines
Maximum 32 detectors and/or manual call
points per line
Monitored sounders line
Auto powered sounders line
External power supply outputs
Programmable open collector output
Level 2 access code.
Easy management
Small size plastic box
Electrical specification
Mains supply voltage: 230V +10%/-15% ~ 50Hz/60Hz
Maximum absorbed current from mains: < 110mA
Min/max output voltage: Min=21V, max=28,5V
Batteries: 2 sealed lead batteries connected in series, 12V 4Ah
Mechanical characteristics
Unit dimensions (in mm): 300 x 260 x 125 (h x w x d)
Material: White plastic box (IP 30)
Climatic characteristics
Operating temperature: -5°C ± 3°C... 40°C ± 2°C
Operating relative humidity: 93% with no condensation
Outputs
1 monitored sounders line: 27V/0,5A
1 auto powered sounders line: 27V/1A
1 external power supply output: 27V/0,5A*
1 resettable power supply output: 27V/0,5A*
1 Alarm NC/NO & 1 Fault NC/NO relay contact: 30V/1A
1 programmable open collector output (repetition of
fault, pre-alarm, alarm, silence buzzer, disable): 30V/30mA
Description
The ALPHA 2 unit is a fire detection panel. It has been developed and engineered according to European
standards: EN 54-2 and EN 54-4.
It has 2 resistive monitored conventional lines which are physically separated. The panel can receive at
maximum 64 detectors and/or manual call points in total.
Each zone has visualization indicators which give immediate signalization of alarm, fault and
enabling/disabling. All signalisations of the panel are available through leds and piezoelectric buzzer.
Control functions are available on a membrane keyboard.
ALPHA 2 is recommended for small conventional installations with 64 points maximum.
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “ALPHA 2 – 2 zones fire detection conventional panel” Cancel reply
Related Products
-
0 out of 5
Honeywell Gent Conventional Control Panel: 13270-02LB
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
-
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
Conventional Smoke Detector GFE-C
Key Features
- Dual LEDs for 360º visibility
- Advanced detection and communication protocols
- Easy installation and maintenance
- Sleek low-profile housing
- Durable sensor head, no need for replacement
- SMD circuit board design. High quality and reliability guaranteed
- Sensor Base Option: Regular GFE Detector Base or Deep Base
-
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)