Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
TECHNICAL SPECIFICATIONS | |
SUPPLY SPECIFICATION | DETAILS |
PRIMARY SUPPLY VOLTAGE - IN | 230 +10% -15% V AC |
PRIMARY SUPPLY VOLTAGE - OUT | 28.5 V DC nominal |
PRIMARY SUPPLY CURRENT - OUT | 1.7 A @ 28.5 V DC nominal (max.) |
SECONDARY SUPPLY VOLTAGE | 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC |
SECONDARY SUPPLY CURRENT OUTPUT | 1.1 Amp Maximum @ 200C |
INTERNAL BATTERY CAPACITY - MAXIMUM | 2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries |
MAINS FUSE | 4 A -250 V Slow Blow - 20 mm |
BATTERY FUSE | 1.6 Amp - Resettable |
DETECTION CIRCUIT SPECIFICATION | |
NUMBER OF CIRCUITS | 2,4 or 8 |
ZONE CURRENT - QUIESCENT / ALARM | 4 mA / 60 mA - Maximum |
MAX. CABLE RESISTANCE / CAPACITANCE | 40 Ohms / 0.470 uF |
END OF LINE MONITORING | Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor |
BS-5839 DETECTOR REMOVAL COMPLIANT | YES provided diodes are fitted to detector base |
DEVICES PER ZONE | 32 Maximum - EN54 pt.2 |
ALARM RESISTANCE VALUE | 270 - 1000 Ohms |
SOUNDER CIRCUIT SPECIFICATION | |
CURRENT OUTPUT | 2 outputs w/ 500mA max. current drive per circuit - fully monitored |
ALARM VOLTAGE / END OF LINE RESISTOR | 27.5 V DC Nominal / 10 K Ohms - 1/4 Watt |
AUXILIARY OUTPUTS SPECIFICATION | |
AUXILIARY RELAY OUTPUT | 1 Fire (COM |
RELAY CONTACT RATING | 50 V DC |
REMOTE INPUT SPECIFICATION | |
EVACUATION (CC) - DAY/ NIGHT MODE | Non-Latching |
RESET | Non-Latching |
MECHANICAL & OPERATING SPEC. | |
HUMIDITY | Max 95% RH Non-Condensing |
PROTECTION | IP30 |
OPERATING TEMPERATURE | -10ºC to 50ºC |
WEIGHT | 1.7 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.) |
DIMENSIONS | 273 (L) x 107 (W) x 404 (H) mm |
COLOUR | Red & White |
Description
ORION
Conventional Fire Detection Panel
The ORION conventional control panel range offers a creatively designed and visually pleasing solution for
smaller cost-conscious projects demanding simplicity of operation. Versions available include 2, 4 and 8 zone
panels and two styles of repeater.
The outstanding programmable features included in this panel range contradict the facilities commonly available
in this type of panel and include: programmable time delay by zone, Day/Night mode, selectable non-latching
zones and coincidence detection.
Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the one
man test mode which provides simple and efficient testing of the system.
Advanced configuration solutions include the following: a dedicated RS232 communication interface allowing
connection of up to 4 remote repeater panels, addressable loop interface modules and multiplexed zonal output
relays; giving one of the most highly advanced levels of system integration and compatibility existing on the
market at this level.
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Global Fire Conventional Panel ORION 2-4-8” Cancel reply
Related Products
-
0 out of 5
ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management -
0 out of 5
Honeywell Gent Conventional Heat Detector : Eco 1005
• Low current draw, Low profile design
• 580C operating temperature
• Operates at 12 and 24VDC
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
• Approved to EN54 –5:2000 Class A1R
• Approved to MED 96/98/EC (Amendment 2009/26/EC)
• Extended warranty -
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
Honeywell Gent Conventional MCP
- Fully compliant with EN54, Part 11
- Re-settable operating element option
- Weather proof IP67
- Semi-flush or surface mounting
- 470 Ohm resistor and Normally Open
contact complete with glass - Resistive and clean contact connections
- Standard MCP, surface mounted
-
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort
Reviews