Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Conventional Sounder VALKYRIE CS
VALKYRIE CS
Conventional Wall Mount Sounder/ Beacon
The VALKYRIE CS is a wall mounted Conventional Sounder/ Beacon with low power consumption. Four different
tones are available and selected using DIL switches 1 and 2.
Both continuous and pulsing outputs are provided via separate negative supply connections allowing for the
presence of differentiated evacuation and alert sounds. -
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort -
0 out of 5
ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management -
0 out of 5
TS1000
Tripod turnstiles are compact and cost-effective entrance solutions. Designing for smooth and silent operation, reducing power consumption, wear and tear. It is suitable for areas with a high traffic.
The TS1000 series, our stainless steel compact version,offer high operating reliability in a small casework, ideal for sites where space is an issue. By receiving a signal from the access control system, or pushing button, it allows the entry of one person in a time. Entering into different directions are electronically controlled. Default mode is to lock the mechanism until a valid authorization signal is received. IIf you want to set one side free, you can adjust the mechanism. In case of emergency, the horizontal arm will drop to allow free passage.
-
0 out of 5
Standard 2-8 Zone Conventional Fire Alarm Panel-C-tech
- Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13. compliance from the BSI.
- Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
- Manufactured by C-TEC in the UK.
- Two detector zone circuits.
- Four conventional sounder circuits*
- Integral 1.5A EN54-4/A2 compliant switch mode PSU.
- Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
- Two on-board relays (Fire and Fault).
- Two open-collector outputs (Remote and Reset).
- ‘Class change’ and alert inputs.
- Installer-friendly design.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
- Low 25mA quiescent current.
- Multiple indicators.
- System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
- Space for two x 12V 3.3Ah VRLA batteries.
- Fully compatible with C-TEC’s ActiV range of conventional fire detectors.
Reviews