Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort -
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
Conventional Smoke Detector GFE-C
Key Features
- Dual LEDs for 360º visibility
- Advanced detection and communication protocols
- Easy installation and maintenance
- Sleek low-profile housing
- Durable sensor head, no need for replacement
- SMD circuit board design. High quality and reliability guaranteed
- Sensor Base Option: Regular GFE Detector Base or Deep Base
-
0 out of 5
HEPHAIS 128 2 Loops Addressable Panel
Main characteristics
2 loops (128 addr./loop) or 4 open circuits (32
det./line)
99 zones, 99 groups of command
1000 memory events
Pre-alarm mode, day/night mode
Manual/automatic activation of sounders line
2 programmable inputs + 5 programmable relay
outputs
Very easy to program and install
Self-learning of detectors on the loop
Programmable by keyboard or software
downloading/uploading
4 lines, 40 characters LCD display -
0 out of 5
Standard 2-8 Zone Conventional Fire Alarm Panel-C-tech
- Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13. compliance from the BSI.
- Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
- Manufactured by C-TEC in the UK.
- Two detector zone circuits.
- Four conventional sounder circuits*
- Integral 1.5A EN54-4/A2 compliant switch mode PSU.
- Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
- Two on-board relays (Fire and Fault).
- Two open-collector outputs (Remote and Reset).
- ‘Class change’ and alert inputs.
- Installer-friendly design.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
- Low 25mA quiescent current.
- Multiple indicators.
- System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
- Space for two x 12V 3.3Ah VRLA batteries.
- Fully compatible with C-TEC’s ActiV range of conventional fire detectors.
Reviews
There are no reviews yet.