Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction -
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
-
0 out of 5
Addressable Indoor sounder AVSA05R
Main characteristics
Addressable independent device
Loop powered
90 dB (+/- 3 dB) at 1 meter
6 tones selectable
Integrated loop isolator
Red or white color
Lateral hearings
Volume control -
0 out of 5
Addressable manual call point DMA05
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version -
0 out of 5
Global Fire Addressable Panel JUNO NET
- Fully expandable system from 1-96 Loops with distributed intelligence for added security
- Up to 256 devices per loop (TBA)
- Up to 96 Loop sounders with 32 individually programmable addresses per Loop
- Compatible with major analogue addressable communications protocols
- 2 Fire output changeover relays and 1 Fault output relay (NC)
- Open collector outputs for Fire, Fault and pre-alarm remote indication
- 2 fully monitored sounder outputs on main panel and each sub panel
- Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card)
- Redundant network communication via RS485, TCP/IP & Fiber Optics
- 384 programmable zones
- 512 fully programmable sounder and I/O groups
- Event Log 2000 entries FIFO
- Backlit LCD display 4 row * 40 characters
- Multiple programming options, onboard keypad, Remote IR(optional), PS2 Keyboard and GFE Connector software
- Windows™ based PC Graphics package ODYSSEY for alarm management and reporting(Optional)
- Multiple Language support (menu selectable)
- MODBUS (ASCII & RTU) and BMS support
Reviews
There are no reviews yet.