Honeywell Gent Conventional Control Panel: 13270-02LB
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
Model | 2 Zone
13270-02LB |
4 Zone
13270-04LB |
8 Zone
13270-08LB |
MAXIMUM LOAD PER ZONE | 3mA | ||
NO. OF SOUNDER CIRCUITS | 2 | 4 | 8 |
MAX. SOUNDER CIRCUIT LOAD | 500mA per circuit max 1A combined | ||
BATTERIES | 2 x 12V, 2.1 Ah min | 2 x 12V, 2.1 Ah min | 2 x 12V, 3.4 Ah |
BATTERY STANDBY | 72 hours (1mA per zone + 0.5A sounder load max) | ||
WEIGHT (APPROX. WITH BATTERIES) | 5.8Kg | 5.8Kg | 6.2 Kg |
CABLE TYPE | BS 6387, 2 core, min 1.5mm2 CSA | ||
OPERATING ENVIRONMENT | Indoor, 0 - 40ºC | ||
CLASS CHANGE FACILITY | Volt free contact - max distance 100m | ||
APPROVALS | BSI Approved (KM 553763) | ||
CPD NO | 0086-CPD-553764 | ||
RELEVANT STANDARD | EN54: Parts 2 &4 |
Description
BSI approved to EN54: Parts 2 & 4, the Xenex control panel can be used on installations meeting BS 5839:Part1. Control panel options for 2-8 zones can be specifi ed.
Designed to simplify system installation, each Xenex panel contains an integral power supply and battery support to drive up to 8 alarm sounder circuits, 2 auxiliary relay contacts, a zone disablement facility and also one-man test and commissioning features.
Utilising LPCB approved conventional smoke or heat detectors, Xenex offers exceptional value for money.
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Honeywell Gent Conventional Control Panel: 13270-02LB” Cancel reply
Related Products
-
0 out of 5
Honeywell Gent Conventional MCP
- Fully compliant with EN54, Part 11
- Re-settable operating element option
- Weather proof IP67
- Semi-flush or surface mounting
- 470 Ohm resistor and Normally Open
contact complete with glass - Resistive and clean contact connections
- Standard MCP, surface mounted
-
0 out of 5
ALPHA 2 – 2 zones fire detection conventional panel
Main characteristics
2 monitored conventional lines
Maximum 32 detectors and/or manual call
points per line
Monitored sounders line
Auto powered sounders line
External power supply outputs
Programmable open collector output
Level 2 access code.
Easy management
Small size plastic box -
0 out of 5
HEPHAIS 1600 Addressable Panel
Main characteristics
400 addressable devices
1000 zones, 256 groups of command
Base: 2 loops (200 addr./ loop) or 4 open circuits (32
det./line)
2 programmable inputs / 2 programmable outputs on the
CPU board
2 programmable inputs on the front board
Jbus protocol for remote monitoring software
Detectors management (day/night, scheduled sensitivity,
pre-alarm, alarm confirmation)
Addressable sounders management
Manual/automatic management of monitored sounders line
Download software
Actuators function (activation/deactivation command
groups) -
0 out of 5
Conventional Smoke Detector GFE-C
Key Features
- Dual LEDs for 360º visibility
- Advanced detection and communication protocols
- Easy installation and maintenance
- Sleek low-profile housing
- Durable sensor head, no need for replacement
- SMD circuit board design. High quality and reliability guaranteed
- Sensor Base Option: Regular GFE Detector Base or Deep Base
-
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
Reviews
There are no reviews yet.