ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
Electrical specification
Mains supply voltage: 230V ~ 50 / 60 Hz
Operating voltage: 27Vdc
Wiring: From 0,5 mm2 (500m max) to 2,5 mm ²
Batteries: 2 x 12V/7,2AH
Maximum current supplied: 1A
Mechanical characteristics
Dimensions (mm) / weight (without batteries): 300x370x118 (h x w x d) / 2Kg
IP rating: IP 31
Climatic characteristics
Operating temperature: 0°C to 50°C
Inputs/outputs
AR4D base detection module: 4 detection lines (128 points)
1 monitored programmable input: external power supply state monitoring (standard configuration), external sounders
line activation, external reset panel
1 monitored sounders line: 24V/450mA
1 monitored external power supply output: 24V/450mA
4 programmable open collector outputs: alarm, pre-alarm, disabled, test, system fault, power supply
fault, fault warning, evacuate, active, buzzer on,
reset: 40V/0,1A
1 Alarm NC/NO & 1 Fault NC/NO relay contact: 30V/1A
Options
REP4R, R4P2, R7P2, & R12P2 4, 7, & 12 potential free contact relays boards 30V/1A
EX4A4 detection module 4 detection lines (32 det./line)
DEAG extinguishing module
- Extinguishing actuators line (solenoid or pyroelectric), 24Vdc/1,2A
- Indicators/sounders line, 24Vdc/1A
- Manual extinguishing line
- Inhibition line
- Pressure contact line
- External power supply
Description
ALPHA 4/8/12, modular, compact and economic, is the adapted solution for small installations.
It is microprocessor controlled with SMD technology and with panel programming it is easy to use and install.
With its 4 zones in the basic version and its design, it is adapted for small installations.
Thanks to its optional modules, ALPHA 4/8/12 can be extended to 12 detection zones maximum (384 conventional points) or 2 extinguishing channels maximum (1 extinguishing channel per extinguishing module). Thanks to its 2 slots ALPHA 4/8/12 can provide the following optimal solutions:
4 detection zones + 2 extinguishing channels
8 detection zones + 1 extinguishing channel
12 detection zones
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “ALPHA 4/8/12 Conventional fire detection panel” Cancel reply
Related Products
-
0 out of 5
Honeywell Gent Conventional Control Panel: 13270-02LB
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
-
0 out of 5
Conventional Smoke Detector GFE-C
Key Features
- Dual LEDs for 360º visibility
- Advanced detection and communication protocols
- Easy installation and maintenance
- Sleek low-profile housing
- Durable sensor head, no need for replacement
- SMD circuit board design. High quality and reliability guaranteed
- Sensor Base Option: Regular GFE Detector Base or Deep Base
-
0 out of 5
TS1000
Tripod turnstiles are compact and cost-effective entrance solutions. Designing for smooth and silent operation, reducing power consumption, wear and tear. It is suitable for areas with a high traffic.
The TS1000 series, our stainless steel compact version,offer high operating reliability in a small casework, ideal for sites where space is an issue. By receiving a signal from the access control system, or pushing button, it allows the entry of one person in a time. Entering into different directions are electronically controlled. Default mode is to lock the mechanism until a valid authorization signal is received. IIf you want to set one side free, you can adjust the mechanism. In case of emergency, the horizontal arm will drop to allow free passage.
-
0 out of 5
Addressable Indoor sounder AVSA05R
Main characteristics
Addressable independent device
Loop powered
90 dB (+/- 3 dB) at 1 meter
6 tones selectable
Integrated loop isolator
Red or white color
Lateral hearings
Volume control -
0 out of 5
Addressable manual call point DMA05
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version
Reviews
There are no reviews yet.