ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
Electrical specification
Mains supply voltage: 230V ~ 50 / 60 Hz
Operating voltage: 27Vdc
Wiring: From 0,5 mm2 (500m max) to 2,5 mm ²
Batteries: 2 x 12V/7,2AH
Maximum current supplied: 1A
Mechanical characteristics
Dimensions (mm) / weight (without batteries): 300x370x118 (h x w x d) / 2Kg
IP rating: IP 31
Climatic characteristics
Operating temperature: 0°C to 50°C
Inputs/outputs
AR4D base detection module: 4 detection lines (128 points)
1 monitored programmable input: external power supply state monitoring (standard configuration), external sounders
line activation, external reset panel
1 monitored sounders line: 24V/450mA
1 monitored external power supply output: 24V/450mA
4 programmable open collector outputs: alarm, pre-alarm, disabled, test, system fault, power supply
fault, fault warning, evacuate, active, buzzer on,
reset: 40V/0,1A
1 Alarm NC/NO & 1 Fault NC/NO relay contact: 30V/1A
Options
REP4R, R4P2, R7P2, & R12P2 4, 7, & 12 potential free contact relays boards 30V/1A
EX4A4 detection module 4 detection lines (32 det./line)
DEAG extinguishing module
- Extinguishing actuators line (solenoid or pyroelectric), 24Vdc/1,2A
- Indicators/sounders line, 24Vdc/1A
- Manual extinguishing line
- Inhibition line
- Pressure contact line
- External power supply
Description
ALPHA 4/8/12, modular, compact and economic, is the adapted solution for small installations.
It is microprocessor controlled with SMD technology and with panel programming it is easy to use and install.
With its 4 zones in the basic version and its design, it is adapted for small installations.
Thanks to its optional modules, ALPHA 4/8/12 can be extended to 12 detection zones maximum (384 conventional points) or 2 extinguishing channels maximum (1 extinguishing channel per extinguishing module). Thanks to its 2 slots ALPHA 4/8/12 can provide the following optimal solutions:
4 detection zones + 2 extinguishing channels
8 detection zones + 1 extinguishing channel
12 detection zones
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “ALPHA 4/8/12 Conventional fire detection panel” Cancel reply
Related Products
-
0 out of 5
Addressable manual call point DMA05
Main characteristics
CE certified according to CPD
Conform with the standards EN54-11, EN54-17, EN54-18
Key for reset
Separate key for test
No break glass
BA9S Waterproof IP65 version -
0 out of 5
Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction -
0 out of 5
HEPHAIS 1600 Addressable Panel
Main characteristics
400 addressable devices
1000 zones, 256 groups of command
Base: 2 loops (200 addr./ loop) or 4 open circuits (32
det./line)
2 programmable inputs / 2 programmable outputs on the
CPU board
2 programmable inputs on the front board
Jbus protocol for remote monitoring software
Detectors management (day/night, scheduled sensitivity,
pre-alarm, alarm confirmation)
Addressable sounders management
Manual/automatic management of monitored sounders line
Download software
Actuators function (activation/deactivation command
groups) -
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
-
You've just added this product to the cart:
Fingerprint Time & Attendance and Access Control Terminal Model: iClock 680
0 out of 5Fingerprint Time & Attendance and Access Control Terminal Model: iClock 680
• Intuitive and stunning UI designed with the most popular and internationalized factor.
• Interface operation adopts modularized hierarchical design. Simpler, Better and More logical.
• Faster matching speed: Less than 1 second.Enhanced Features and Performance
• User validity settings.
• Data backup and retreival.
• Advanced User ID consisted of letters and numbers.• Chip encryption for firmware protection.
• More flexible menu configuration: double line text display.
• External printer for attendance records output (Optional).
• Optional integrated Wi-Fi\GPRS.
• Relay contacts for alarm, bell, lock, exit, switch, etc.Excellent Expand-ability
- Easy to extend functions and customize customers demand.
- For Wiegand-in, Wiegand-out, door lock connection, alarm, and bell.
Reviews