Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Conventional MCP GFE-MCPE
GFE-MCPE
Conventional Manual Call PointThe GFE-MCPE-C is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,
compatible with all GFE Conventional Control panels. A bi-colour LED flashes Green when the unit is connected to a
control panel and is illuminated Red when in Alarm.
The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation and
reduces malicious activations as two actions are required in order to activate the device. This unit can be both
surface and flush mounted and it can be easily reset using the supplied key after activation. -
0 out of 5
Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction -
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
ALPHA 2 – 2 zones fire detection conventional panel
Main characteristics
2 monitored conventional lines
Maximum 32 detectors and/or manual call
points per line
Monitored sounders line
Auto powered sounders line
External power supply outputs
Programmable open collector output
Level 2 access code.
Easy management
Small size plastic box -
0 out of 5
ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
Reviews
There are no reviews yet.