ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
Electrical specification
Mains supply voltage: 230V ~ 50 / 60 Hz
Operating voltage: 27Vdc
Wiring: From 0,5 mm2 (500m max) to 2,5 mm ²
Batteries: 2 x 12V/7,2AH
Maximum current supplied: 1A
Mechanical characteristics
Dimensions (mm) / weight (without batteries): 300x370x118 (h x w x d) / 2Kg
IP rating: IP 31
Climatic characteristics
Operating temperature: 0°C to 50°C
Inputs/outputs
AR4D base detection module: 4 detection lines (128 points)
1 monitored programmable input: external power supply state monitoring (standard configuration), external sounders
line activation, external reset panel
1 monitored sounders line: 24V/450mA
1 monitored external power supply output: 24V/450mA
4 programmable open collector outputs: alarm, pre-alarm, disabled, test, system fault, power supply
fault, fault warning, evacuate, active, buzzer on,
reset: 40V/0,1A
1 Alarm NC/NO & 1 Fault NC/NO relay contact: 30V/1A
Options
REP4R, R4P2, R7P2, & R12P2 4, 7, & 12 potential free contact relays boards 30V/1A
EX4A4 detection module 4 detection lines (32 det./line)
DEAG extinguishing module
- Extinguishing actuators line (solenoid or pyroelectric), 24Vdc/1,2A
- Indicators/sounders line, 24Vdc/1A
- Manual extinguishing line
- Inhibition line
- Pressure contact line
- External power supply
Description
ALPHA 4/8/12, modular, compact and economic, is the adapted solution for small installations.
It is microprocessor controlled with SMD technology and with panel programming it is easy to use and install.
With its 4 zones in the basic version and its design, it is adapted for small installations.
Thanks to its optional modules, ALPHA 4/8/12 can be extended to 12 detection zones maximum (384 conventional points) or 2 extinguishing channels maximum (1 extinguishing channel per extinguishing module). Thanks to its 2 slots ALPHA 4/8/12 can provide the following optimal solutions:
4 detection zones + 2 extinguishing channels
8 detection zones + 1 extinguishing channel
12 detection zones
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “ALPHA 4/8/12 Conventional fire detection panel” Cancel reply
Related Products
-
0 out of 5
Conventional MCP GFE-MCPE
GFE-MCPE
Conventional Manual Call PointThe GFE-MCPE-C is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,
compatible with all GFE Conventional Control panels. A bi-colour LED flashes Green when the unit is connected to a
control panel and is illuminated Red when in Alarm.
The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation and
reduces malicious activations as two actions are required in order to activate the device. This unit can be both
surface and flush mounted and it can be easily reset using the supplied key after activation. -
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort -
0 out of 5
Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version -
0 out of 5
Honeywell Gent Conventional Sounder CWSO-RR-S1
- Simple, Fast, Flexible Installation
- Modern design eliminates need for device orientation.
- Designed with full range of common fixing centers.
- Approved to EN54-3.
- Superior sound output and low current consumption.
- 32 tones all approved to EN54-3.
- Suitable for wall and ceiling mount applications.
- Optimised for 12V and 24V systems
- Environmental: RoHS, WEEE
-
0 out of 5
Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction
Reviews
There are no reviews yet.